抽象的

Experimental Evaluation of Water Content In Transformer Oil

PankajShukla, Y.R. Sood, R.K. Jarial

This paper presents experimental research on temperature dependency of water content in mineral transformer oils. Moisture sensor measurements (online measurement) and absolute water content determination by Karl Fisher titration method (off-line method) were performed in the laboratory to investigate solubility of different types of mineral transformer oils. Results of experiments explain that preset moisture solubility model of moisture sensor affects the accuracy of water content determination. Test setup and procedure for verification and calibration of moisture sensor with specific-oil solubility parameters is described then tested and evaluated. This allows greater accuracy of online water content monitoring in the operating transformers under the changing temperature conditions.

索引于

学术钥匙
研究圣经
引用因子
宇宙IF
参考搜索
哈姆达大学
世界科学期刊目录
学者指导
国际创新期刊影响因子(IIJIF)
国际组织研究所 (I2OR)
宇宙

查看更多